PLANT SUMMARY
Containment
Containment Type:
Ice Condenser
Design Pressure:
15 psig
Steam Generator
Steam Generator Model:
Number of Steam Generators:
4
Number of Main Steam Isolation Valves:
4
Fuel
No. of Fuel Assemblies:
193
No. of Fuel Rods per Assembly:
264
Chemical and Volume Control System
No. of Centrifugal Pumps:
2
No. of Positive Displacement Pumps:
1
Pump Design Flow Rate:
150 gpm @ 5800 ft
98 gpm @ 5800 ft (PDP)
High Head (Safety) Injection System
No. of Pumps:
2 (same as CVCS Centrifugal Charging Pumps)
Pump Design Flow Rate:
150 gpm @ 5800 ft
Pump Shutoff Head:
6000 ft
Intermediate Head (Safety) Injection System
No. of Pumps:
2
Pump Design Flow Rate:
400 gpm @ 2600 ft
Pump Shutoff Head:
1520 psi
Low Head (Safety) Injection System (LHI)
No. of Pumps:
2
Pump Shutoff Head:
Residual Heat Removal System
RHR and LHI utilizes the same Pumps?
Yes
No. of Pumps:
2
Pump Shutoff Head:
Main Feedwater
Condensate
No. of Pumps:
3
Pump Shutoff Head:
245 psig
Condensate Booster
No. of Pumps:
3
Pump Shutoff Head:
408.5 psig
Main Feedwater
No. of Pumps:
2 Steam Driven
Startup Feedwater
No. of Pumps:
None
Aux Feedwater System
Number of Motor Driven Pumps:
2
Capacity:
450 gpm each
Number of Turbine Driven Pumps:
1
Capacity:
900 gpm
Aux Feedwater Supply Source
Name:
Aux Feed CST (1 for both units) -- 42,500 gal
Name:
Upper Surge Tanks 1A & 1B--85,000 total
Name:
Condenser Hotwell--170,000 gals
(at normal operating level)
Name:
Nuclear Service Water-- 1.8 x 108 gals
Borated Water Sources and Design Capacities
Name:
Four Accumulators
Name:
Two Boric Acid Tanks
Name:
Refueling Water Storage Tank--95,000 gal
Class 1E Emergency Power
No. of Class-1E Diesel Generators (EDG):
4
No. Shared per Plant Site:
0
No. Dedicated per Unit:
Two
Diesel Manufacturers:
Nordberg
Other Sources of On Site Emergency Power:
None |
GENERAL INFORMATION
Plant Name: McGuire - Unit 1
Docket No.: 50-369
Owner/Operator: Duke Power Company
Other Plants On Site: McGuire - Unit 2
Site Location/Address: 17 miles Northwest of Charlotte,
NC.
Facility Licensed Thermal Power Limit:
(Ref: License) 3411 MWt
Main Turbine Generator Rated Output:
1129 MWe
Ultimate Heat Sink -
Supply to Main Turbine Condenser:
Lake Norman
Ultimate Heat Sink -
Supply to ECCS Service Water System:
Lake Norman/Standby Nuclear Service Water Pond (Two bodies of water serve
as a heat sink for components cooled by the Nuclear Service Water system.
Lake Norman is the normal source of nuclear service water. Should
Lake Norman be lost due to a seismic event in excess of the design of Cowans
Ford Dam; the Standby Nuclear Service Water Pond (SNSWP) would serve as
the heat sink.)
PWR Type:
4-loop
NSSS Vendor:
Westinghouse
Turbine Generator:
Westinghouse
Arch. Engr.:
Duke Power Company
Constructor:
Duke Power Company
Date of Operating License Issuance:
07/08/81
Date of Commercial Operation:
12/01/81
|